Sign In | Join Free | My infospaceinc.com
China Guangzhou Xingjin Fire Equipment Co.,Ltd. logo
Guangzhou Xingjin Fire Equipment Co.,Ltd.
Guangzhou Xingjin Fire Equipment Co.,Ltd
Verified Supplier

11 Years

Home > FM200 Hanging System >

Wall-mounted FM200 Automatic Fire Suppression System

Guangzhou Xingjin Fire Equipment Co.,Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now

Wall-mounted FM200 Automatic Fire Suppression System

Brand Name : XINGJIN

Model Number : XQQW8L/10L/16L/20L/30L/40L

Certification : GSG\TUV\ I S O 9 0 0 1, 1 4 0 0 1, 4 5 0 0 1

Place of Origin : Guangzhou,China

MOQ : 5 set

Price : USD69-160/set

Payment Terms : T/T,L/C

Supply Ability : 30000set/month

Delivery Time : 15-20days

Packaging Details : Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper

Tank size : 8Ltr, 10Ltr, 16Ltr, 20Ltr, 30Ltr

Storage pressure : 1.6mpa

Maximum working pressure : 2.5mpa

Discharge time : ≤10s

Maximum filling Density : 1kg/L

Contact Now

Wall-mounted FM200 Automatic Fire Suppression System


Product Description:

FM200 (HFC-227ea) is a colourless, odourless, non-corrosive, and non-conductive clean agent that leaves no residue after discharge. It has zero Ozone Depletion Potential (ODP), making it an environmentally friendly fire extinguishing solution. These unique properties make it particularly suitable for protecting high-risk areas where electrical fires are likely to occur.

System Types:
The FM200 hanging fire suppression equipment is available in two activation types: temperature‑sensing (thermal) and electromagnetic (electric).
Temperature-Sensing Type (Fixed Temperature)
The suspended HFC-227ea fire extinguishing device (fixed temperature) operates using a temperature‑sensitive glass bulb located within the valve. During a fire, when the ambient temperature reaches approximately 68°C, the liquid inside the bulb expands, causing the bulb to rupture. This opens the valve and releases the extinguishing agent.

Electromagnetic Type (Electric)
The suspended HFC-227ea fire extinguishing device (electromagnetic) consists of an agent storage tank, electromagnetic actuator, nozzle, pressure indicator, and signal feedback components. It can be ceiling‑mounted or wall‑mounted and is designed to work in conjunction with fire detection and alarm devices such as smoke detectors, manual call points, alarm bells, audible alarms, and fire alarm control panels.
Wall-mounted FM200 Automatic Fire Suppression System
Suspended heptafluoropropane fire extinguishing device
(fixed temperature type)
Suspended heptafluoropropane fire extinguishing device
(electromagnetic type)


System Compositions:




The ceiling‑mounted FM200 automatic fire suppression system mainly comprises:

  • One spherical pressure vessel
  • Fire extinguishing agent (HFC-227ea / FM200)
  • Hanging mounting bracket
  • Thermal sensor (a small glass tube filled with a temperature‑sensitive liquid)

FM200 hanging fire suppression equipment can be directly integrated with an alarm system. Our company offers a complete range of alarm system equipment. Please contact us if you are interested.





Wall-mounted FM200 Automatic Fire Suppression System


Activation Methods:

Temperature Control (Thermal Activation)
This fire extinguishing controller relies on the valve's temperature‑sensitive glass bulb. During a fire, when the temperature reaches approximately 68°C, the bulb automatically ruptures and releases the fire extinguishing agent.

Electromagnetic Control (Electric Activation)
Electromagnetic control is available in two modes: automatic and manual.

Automatic Mode:

The controller is equipped with both a smoke detector and a fixed‑temperature heat detector. A control mode selector is provided on the controller.

  • When the selector is set to the "Automatic" position, the system operates in automatic mode.
  • If only one detector generates a fire signal, the controller will emit an audible and visual alarm to notify personnel of an abnormal condition, but will not activate the fire extinguishing device.
  • If fire extinguishing is confirmed necessary, press the "Emergency Start Button" to manually activate the system.
  • When both detectors simultaneously emit fire signals, the controller:
    1.ounds audible and visual alarms to warn personnel and prompt evacuation
    2.Issues linkage commands to shut down fans, fire dampers, and other connected equipment
    3.After a preset delay (typically 30 seconds), issues a fire extinguishing command, activating the solenoid valve and container valve to release the agent
  • If activation is no longer required during the alarm delay period, press the "Emergency Stop Button" (located outside the protected area or on the control panel) to cancel the extinguishing command.

Manual Mode:

  • When the selector is set to the "Manual" position, the system operates in manual control mode.
  • If fire detectors generate an alarm signal, the controller will emit audible and visual alarms but will not activate the extinguishing device.
  • After personnel have visually confirmed a fire, they can press the "Emergency Start Button" (outside the protected area or on the control panel) to activate the system and release the agent.
  • The alarm signal will continue until manually reset.

Important Note: Regardless of whether the system is in automatic or manual mode, pressing any emergency start button will immediately activate the fire extinguishing device and release the agent. The controller will then enter the fire extinguishing alarm state.

Packaging and Shipping for Inert Gas Fire Suppression System
Packaging:

The FM200 fire suppression system is carefully packaged to ensure safe delivery and handling. The packaging includes:

  • Heavy‑duty cardboard box
  • Bubble wrap
  • Protective foam inserts
  • Instruction manual


Shipping:
We offer worldwide shipping for our FM200 fire suppression system. All shipments are sent via reliable and trusted courier services to ensure timely and secure delivery. Customers will receive a tracking number by email once their order has been shipped.

Special Handling Instructions:
If your shipment requires any special handling instructions, please contact us at least 24 hours before dispatch. We will do our best to accommodate your request.
Wall-mounted FM200 Automatic Fire Suppression System



Why Choose Us
Wall-mounted FM200 Automatic Fire Suppression System



Product Tags:

Wall-mounted FM200 fire suppression

      

Automatic FM200 hanging system

      

FM200 fire suppression with warranty

      
Quality Wall-mounted FM200 Automatic Fire Suppression System for sale

Wall-mounted FM200 Automatic Fire Suppression System Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Guangzhou Xingjin Fire Equipment Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)